Failures and troub leshooting
Overcurrent fault
2017-02-10
Check points:
1 heavy load start and acceleration time is short;
2 load light, check parameter settings;
3 is there an output short circuit;
4 the load is changing rapidly, the motor is locked;
5 the grid voltage is low, the power grid voltage sags;
6 is the use of DC braking, DC brake cut frequency;
Treatment method:
1 extend the acceleration time, switch to vector control mode, the use of large file converter;
2.VF control: reduce the VF curve, reduce the torque value;
Vector control: set the correct motor parameters to reduce load compensation;
3 confirm whether the wiring is normal, the output line is bad insulation;
4 eliminate load changes;
5 to ensure that the power grid to normal or reduce load, confirm the existence of high power equipment around the sudden start;
6 reduce the DC braking and reduce the DC braking frequency;